CueServer 2 provides up to eight low-voltage contact-closure inputs. These inputs are designed for connecting switches, buttons, motion detectors, sensors, and most anything that makes an electrical connection between two conductors.
Each contact-closure input can be programmed with any of the available CueScript actions and/or rules to automate any kind of action in CueServer.
Each input floats up to a voltage around 3.3V DC through a weak pull-up resistor. When that input is shorted-to-ground, the CueServer device detects this drop in voltage as a “contact closure”.
Specifications
| CS-900 | CS-920 | CS-940/950 | |
|---|---|---|---|
| Contact Closure Inputs | 8 | 2 | 8 |
| Connector | 10-Position Pluggable Terminal Block | 8-Position Pluggable Terminal Block (shared with other I/O) |
12-Position Pluggable Terminal Block (shared with RS-232 port) |
|
|
|
|
| Pinout | 1 = Common (Ground) 2 = Contact 1 3 = Contact 2 4 = Contact 3 5 = Contact 4 6 = Contact 5 7 = Contact 6 8 = Contact 7 9 = Contact 8 10 = Common (Ground) |
1 = Contact 1 2 = Contact 2 3 = Common (Ground) 4 = RS-232 Transmit 5 = RS-232 Receive 6 = Aux +5VDC Output 7 = Output 1 8 = Output 2 |
1 = Common (Ground) 2 = Contact 1 3 = Contact 2 4 = Contact 3 5 = Contact 4 6 = Contact 5 7 = Contact 6 8 = Contact 7 9 = Contact 8 10 = RS-232 Common 11 = RS-232 Transmit 12 = RS-232 Receive |